Outdoor HVAC GFCI requirement: where Michigan stands now

Mir · · 6 min read

Topics: Michigan,Hvac,Electrical code,Heat pumps,Trades

The outdoor HVAC GFCI requirement now applies in most of Michigan. The National Electrical Code's exemption for outdoor air conditioners and heat pumps, 210.8(F) Exception No. 2, expired on September 1, 2026. Michigan enforces the 2023 NEC, has no state amendment to that section that we could find, and is not on the trade association list of states that changed it. On September 18 an NFPA panel turned down a two-year extension on a 10 to 10 vote. For a Michigan HVAC or electrical contractor, that means new and replaced outdoor units on dwellings need ground-fault protection, starting with this heating season, when a heat pump that trips its breaker is a no-heat call.

In short

  • The exemption for listed HVAC equipment expired on September 1, 2026, in the 2020, 2023 and 2026 editions of the NEC (NFPA, 2026).
  • The extension to September 1, 2028 failed when the panel's technical vote split 10 to 10 (ACCA, 2026).
  • 19 states had amended or delayed the rule by September 30, 2026; Ohio and Wisconsin are on the list, Michigan is not (HARDI, 2026).
  • A GFCI breaker install runs $307 to $373 per breaker as a national average (Fixr, 2026).
Aerial view of a snow-dusted subdivision in Novi, Michigan, with brick colonial houses along a curving street
Every condenser behind these houses that gets replaced from now on is a GFCI question for the inspector. Photo: SAIF SIDDIQUE, Pexels.

What the outdoor HVAC GFCI requirement says

Section 210.8(F) requires GFCI protection for outdoor outlets at dwellings supplied by single-phase branch circuits of 150 volts or less to ground. "Outlet" includes the hard-wired connection to an outdoor condenser or heat pump. The code then carved out an exception: "Ground-fault circuit-interrupter protection shall not be required for listed HVAC equipment. This exception shall expire September 1, 2026." That sentence sits in the 2020, 2023 and 2026 editions alike, as NFPA's own TIA document shows.

The exception existed because the equipment and the breakers did not get along. ACHR News reported on September 11, 2026, quoting ACCA, that "some single-speed and inverter-driven equipment continues to trip standard GFCIs when there is nothing wrong with the installation." AHRI's submission to NFPA describes the cause as high-frequency leakage current from inverter drives, especially at startup, that GFCI sensing can misread.

Where Michigan stands

Michigan's electrical code is Part 8 of the construction code rules. Rule R 408.30801 adopts "the national electrical code 2023 second printing edition, including TIA 70-23-1 to 70-23-13," with exceptions only in Article 80 and section 90.6. Those rules took effect on March 12, 2024, according to ICC-NTA. None of the listed exceptions touch 210.8.

LARA has also published draft Part 8 rules, dated August 19, 2026, that would move Michigan to the 2026 NEC. The draft amends a handful of rules, among them the adoption rule, the authority rule and disconnecting means. It does not amend 210.8. And the 2026 edition's exception carries the same September 1, 2026 date. So the code update does not bring the exemption back either.

HARDI's state tracker, updated September 30, 2026, lists 19 states that amended 210.8(F) for outdoor HVAC equipment, including neighbouring Ohio and Wisconsin. Michigan is not one of them. Our reading is that the requirement is live here. The person whose reading counts is the inspector who signs off your permit, so ask before you quote, not after the rough-in.

The extension that failed

AHRI asked NFPA for Tentative Interim Amendment 1924, which would have changed the expiry date to September 1, 2028 in all three editions. ACCA's September 25, 2026 post reports the result: "On technical merit, the panel vote was evenly divided, 10-10," short of the threshold a TIA needs. The panel denied it on September 18.

ACCA and AHRI appealed. ACCA asked the Standards Council to "approve TIA 1924 and extend the exception through September 1, 2028" and requested a hearing. As of September 25, homepros.news reported, "no hearing for the submitted appeals has been arranged," and the next Standards Council meeting is scheduled for December 15. Even a win there would need Michigan to adopt the amendment before an inspector here could apply it. Plan for this winter on the rule as written.

A building inspector in a yellow hard hat and high-visibility vest checking a doorway with a clipboard
The code text is settled for now. How your local inspector reads it is the conversation to have first. Photo: RDNE Stock project, Pexels.

What a Michigan HVAC shop changes this month

  1. Ask each inspector you work with how they read 210.8(F) after September 1. Write the answer down with the jurisdiction and date. Detroit, Oakland County townships and state-inspected areas can differ in practice even under one code.
  2. Update the quote template. Every new or replacement outdoor unit on a dwelling gets a GFCI line, with the breaker type the equipment manufacturer lists as compatible. A customer who sees it on the quote does not argue about it on the invoice.
  3. Check the installation instructions for the breaker. If the manufacturer names a compatible GFCI breaker, quote that one. The cheapest breaker on the truck is not automatically the right one.
  4. Brief whoever answers the phone after hours. The script for "my heat pump stopped" now includes "check whether the breaker in the panel has tripped, and tell us if it has." That one question separates a reset from a truck roll.
  5. Log every trip callback. Date, model, breaker, outdoor temperature, and whether a reset held. If nuisance tripping is real on certain equipment, your log is the evidence a manufacturer or inspector will ask for.

The mistake most shops make at step 4

They treat a GFCI trip as a homeowner problem. The homeowner sees no heat, resets the breaker, it trips again at 3 a.m., and by morning they have called whoever answered first. A heat pump in a Michigan January cannot sit tripped until Monday. Decide now who gets that call, what they ask, and when a tech goes out. That is the part of this code change no breaker fixes.

A man wrapped in a heavy patterned sweater talking on a mobile phone in a cold room
The first cold night after an install is when a nuisance trip turns into a phone call. Photo: Thirdman, Pexels.

Where we fit

The code is your electrician's and your inspector's call. The phone is where we help. Our phone and front desk work answers every call at any hour in your shop's own voice, asks whether the breaker tripped, and routes a no-heat call to the tech on call instead of a voicemail box. For more on what the calls you miss cost, see the cost of missed calls for a small business, and for the rest of what we build for trades, the services overview.

Ask your inspector this week. The first cold snap will not wait for the appeal.

Sources

  1. NFPA, Proposed TIA 1924 to NFPA 70, 210.8(F) Exception No. 2 (2020, 2023 and 2026 editions; comment closing September 9, 2026) (2026)
  2. ACCA HVAC Blog, ACCA appeal of the NFPA ruling on TIA 1924 (September 25, 2026) (2026)
  3. homepros.news, Trade groups appeal after code panel rejects GFCI extension for outdoor HVAC equipment (September 25, 2026) (2026)
  4. ACHR News, ACCA offers guidance as GFCI exemption expires (September 11, 2026) (2026)
  5. HARDI, What HVACR Distributors Need to Know About Outdoor HVAC GFCI Requirements (updated September 30, 2026) (2026)
  6. Mich. Admin. Code R 408.30801, National electrical code adoption by reference (via Cornell LII) (2024)
  7. ICC-NTA, Michigan Electrical Code, Part 8 rules 2023 (effective March 12, 2024) (2024)
  8. Michigan LARA, Part 8 Electrical Code draft rules, strike and bold (August 19, 2026) (2026)
  9. Fixr, New Electrical Code 2026: What Homeowners Need for HVAC and More (September 17, 2026) (2026)

Questions people ask

Does an outdoor AC condenser or heat pump need GFCI protection in Michigan now?

Very likely, for new and replaced equipment. Michigan's electrical code adopts the 2023 National Electrical Code, whose 210.8(F) Exception No. 2 exempted listed HVAC equipment from GFCI protection only until September 1, 2026. Michigan's rules contain no amendment to 210.8(F) that we could find, and HARDI's September 30, 2026 list of states that changed the rule does not include Michigan. Confirm with the inspector who will sign off the job.

Was the outdoor HVAC GFCI exemption extended?

Not so far. An NFPA panel considered TIA 1924, which would have moved the expiry to September 1, 2028, and the technical vote split 10 to 10, so it failed on September 18, 2026. ACCA and AHRI appealed to the NFPA Standards Council, whose next meeting was scheduled for December 15, 2026.

Why do GFCI breakers trip on heat pumps and inverter air conditioners?

Inverter-driven equipment can leak high-frequency current to ground during normal operation, especially at startup, and standard GFCI sensing can read that as a fault. ACCA's technical staff said in September 2026 that some single-speed and inverter-driven equipment still trips standard GFCIs when nothing is wrong with the installation.

How much does a GFCI breaker for an AC unit cost to install?

Fixr put the national average cost to install a GFCI circuit breaker at $307 to $373 per breaker as of May 2026. The equipment-compatible breaker a manufacturer specifies can differ, so check the unit's installation instructions before quoting.